The band above your windows carries the wall over the opening, and the sunshade hangs from it with nothing underneath. One rule saves both: enough bearing for the lintel, and main steel on top of the sunshade - forget that and it will surely droop.
Above every door and window the wall needs a bridge - the lintel - and outside, a sunshade keeps sun and rain off the opening. Both are small castings, and both fail in the same two well-known ways on careless sites: too little bearing, and sunshade steel in the wrong place.
A lintel should sit at least 150 mm into the wall on each side (or as much as its own depth), so the load spreads into the masonry. The sunshade is a cantilever - held from one side only - so the pull is at its top. Its main steel runs near the top surface and bends well back into the lintel. Sunshade steel on top: forget this one thing and the sunshade will surely droop.
Two mistakes that cannot be fixed later
- Too little lintel bearing: the load concentrates at the corners of the opening, and diagonal cracks run through the bricks. Keep at least 150 mm inside the wall each side.
- Sunshade steel placed low: in a cantilever the tension is on top; steel placed low does nothing, the sunshade droops and a crack opens at its root. Main steel sits 15-20 mm below the top surface, with an L-bend anchored into the lintel.
The right sequence, in six steps
- Fit the frame and raise the wall to lintel level.
- Erect a box for the lintel and a board for the sunshade, props below.
- Place the lintel cage, with the sunshade's top steel bent into the lintel.
- Cast the lintel and sunshade together in one go.
- Cure with wet gunny bags for 7-10 days.
- Strike the lintel shuttering after 7 days - but sunshade props stay 14 days.
Numbers worth remembering
- Lintel bearing each side: at least 150 mm
- Cover on the lintel cage: 25 mm (IS 456, Table 16)
- Sunshade thickness: about 75-100 mm, as per drawing
- Sunshade main steel: in the top layer (IS 456, cantilever action)
- Removing sunshade props: not before 14 days (IS 456, Table 11)
Site checklist
- Lintel level equal on both sides; bearing at least 150 mm
- Cover blocks in the cage; sunshade steel on top, bent into the lintel
- A slight outward slope in the sunshade shuttering so water runs off
- Cast in one go; props not removed early
This guide is adapted from BHK99's illustrated site handbook series. The next layer of the wall's life is plaster; for the structure these rest on, see RCC beams.